P850-1

Minimum Rating

770.0 kVA / 616.0 kW

Maximum Rating

850.0 kVA / 680.0 kW

Emissions/Fuel Strategy

Fuel Optimised


Specifications

Overview

The new 350 – 938 kVA industry leading power range is the result of a continued focus on performance, durability and serviceability combined with the most advanced production methods to deliver power you can trust.

Generator Set Specifications

Minimum Rating 770.0 kVA / 616.0 kW
Maximum Rating 850.0 kVA / 680.0 kW
Emissions/Fuel Strategy Fuel Optimised
50 Hz Prime 770.0 kVA / 616.0 kW
50 Hz Standby 850.0 kVA / 680.0 kW
60 Hz Prime – / –
60 Hz Standby – / –
Frequency 50 Hz
Speed 1500 RPM
Voltage 230-400 Volts

Engine Specifications

Engine Model Perkins® 2806A-E18TTAG5
Bore 145.0 mm (5.7 in)
Stroke 183.0mm (7.2 in)
Governor Type Electronic
Displacement 18.1l (1104.5 cu. in)
Compression Ratio 14.0:1

Benefits & Features

The Story

The 350 – 938 kVA range from FG Wilson is designed by our expert engineers to deliver power you can trust. With an enhanced choice of power nodes, this range is engineered for optimum performance in diverse applications. Expert Design´┐Ż Trusted Power

 

FG Wilson Diesel Engine

The Perkins 2000 Series offers excellent performance from the well-proven 6 cylinder 13, 15 & 18 litre in-line diesel engines. Developed from a proven heavy-duty industrial base, the engine offers superior performance and reliability. Its premium design ensures economic and durable operation, low emissions and advanced performance and reliability.

 

Alternator

Benefiting from a choice of leading alternators, the range incorporates the FG Wilson alternator as standard.

 

PowerWizard 1.1+

The FG Wilson PowerWizard range of digital control panels, combine straightforward menu navigation with advanced metering and protection technology. They are used in automatic mains failure applications in conjunction with transfer panels. Our PowerWizard range allows you to monitor and control your generator set with ease, whilst ensuring your unit operates within safe parameters and provides important diagnostic information when needed.

 

Testing & Validation

Fully prototype tested with certified torsional vibration analysis available

 

Standard Reference Conditions

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

 

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

Equipment

P850-1 Standard Equipment
Engine
Air Cleaner
Lube oil drain valve
Engine filled with lubrication oil
High Coolant Temperature Shutdown
Low Oil Pressure Shutdown
Engine mounted battery charging alternator

Cooling
Package mounted radiator
Radiator fan and charging alternator guards
Coolant Drain Valve
Cooling System filled with Coolant mix

Exhaust
Exhaust flange outlet
Exhaust bellows and gasket

Fuel
8 Hr Fuel Tank
BSP Fuel Sockets

Alternator
FG Wilson
SHUNT Excitation
IP23 Protection

Control Panel
PowerWizard 2.1+

Mounting
Robust steel constructed base frame
Base frame drag and lift points
Captive linear vibration isolators between base and engine-generator
Battery Tray and Cables

P850-1 Optional Equipment
Exhaust
Industrial, Residential, Critical Silencers

Alternator
Quadrature Droop Kit (AR6)
Anti-Condensation Heater and Panel Circuitry
AREP / PMG excitation
AVR Upgrades
Three phase sensing
Oversize Alternator
Coastal ingress protection alternator
Leroy Somer

Control Panels
PowerWizard 2.1
easYgen-2500

Starting/Charging
Heavy duty dry battery
Battery charger with auto boost

General
Upgrade to Standard Set for “CE” Certification
EEC Declaration of Conformity
Dual wall base tank (8 hrs)
Sound attenuated or High ambient enclosures – Coming Soon
Battery isolator switch